Carbon monoxide detector

Carbon monoxide detector
Carbon Monoxide detector connected to a North American power outlet

A carbon monoxide detector or CO detector is a device that detects the presence of the carbon monoxide (CO) gas in order to prevent carbon monoxide poisoning. CO is a colorless and odorless compound produced by incomplete combustion. It is often referred to as the "silent killer" because it is virtually undetectable without using detection technology.[1] Elevated levels of CO can be dangerous to humans depending on the amount present and length of exposure. Smaller concentrations can be harmful over longer periods of time while increasing concentrations require diminishing exposure times to be harmful.[2]

CO detectors are designed to measure CO levels over time and sound an alarm before dangerous levels of CO accumulate in an environment, giving people adequate warning to safely ventilate the area or evacuate. Some system-connected detectors also alert a monitoring service that can dispatch emergency services if necessary.

While CO detectors do not serve as smoke detectors and vice versa, dual smoke/CO detectors are also sold. Smoke detectors detect the smoke generated by flaming or smoldering fires, whereas CO detectors detect and warn people about dangerous CO buildup caused, for example, by a malfunctioning fuel-burning device. In the home, some common sources of CO include open flames, space heaters, water heaters, blocked chimneys or running a car inside a garage.[3]

Contents

Installation

The devices, which retail for $15–$60USD and are widely available, can either be battery-operated or AC powered (with or without a battery backup). Battery lifetimes have been increasing as the technology has developed and certain battery powered devices now advertise a battery lifetime of over 6 years. Some smoke detectors are equipped with an internal rechargeable battery backup that recharges when the detector is receiving AC power. All CO detectors have "test" buttons like smoke detectors.

CO detectors can be placed near the ceiling or near the floor because CO is very close to the same density as air[4][5].

Since CO is colorless, tasteless and odorless (unlike smoke from a fire), detection in a home environment is impossible without such a warning device. It is a highly toxic inhalant and attaches to the hemoglobin(in the blood stream) with an affinity 200x stronger than oxygen[6], producing inadequate amounts of oxygen traveling through the body. In North America, some state, provincial and municipal governments have statutes requiring installation of CO detectors in construction - among them, the U.S. states of Alaska, California, Colorado, Connecticut, Florida, Georgia, Illinois, Maryland, Massachusetts, Minnesota, New Jersey, New York, Oregon, Rhode Island, Texas, Vermont, Virginia, Wisconsin and West Virginia, as well as New York City and the Canadian province of Ontario.[7]

When carbon monoxide detectors were introduced into the market, they had a limited lifespan of 2 years. However technology developments have increased this and many now advertise up to 7 years.[8] Newer models are designed to signal a need to be replaced after that time-span although there are many instances of detectors operating far beyond this point.

According to the 2005 edition of the carbon monoxide guidelines, NFPA 720[9], published by the National Fire Protection Association, sections 5.1.1.1 and 5.1.1.2, all CO detectors “shall be centrally located outside of each separate sleeping area in the immediate vicinity of the bedrooms,” and each detector “shall be located on the wall, ceiling or other location as specified in the installation instructions that accompany the unit.”

According to the 2009 edition of the IRC[10], published by the International Code Council, section R315.1, "For new construction, an approved carbon monoxide alarm shall be installed outside of each separate sleeping area in the immediate vicinity of the bedrooms in dwelling units within which fuel-fired appliances are installed and in dwelling units that have attached garages", and section 315.2, "Where work requiring a permit occurs in existing dwellings that have attached garages or in existing dwellings within which fuel-fired appliances exist, carbon monoxide alarms shall be provided in accordance with Section R315.1."

Installation locations vary by manufacturer. Manufacturers’ recommendations differ to a certain degree based on research conducted with each one’s specific detector. Therefore, make sure to read the provided installation manual for each detector before installing.

CO detectors are available as stand-alone models or system-connected, monitored devices[11]. System-connected detectors, which can be wired to either a security or fire panel, are monitored by a central station. In case the residence is empty, the residents are sleeping or occupants are already suffering from the effects of CO, the central station can be alerted to the high concentrations of CO gas and can send the proper authorities to investigate.

The gas sensors in CO alarms have a limited and indeterminable life span, typically two to five years. The test button on a CO alarm only tests the battery and circuitry not the sensor. CO alarms should be tested with an external source of calibrated test gas, as recommended by the latest version of NFPA 720. Alarms over five years old should be replaced but they should be checked on installation and at least annually during the manufacturers warranty period.

Sensors

Early designs were basically a white pad which would fade to a brownish or blackish color if carbon monoxide was present. Such chemical detectors were cheap and were widely available, but only give a visual warning of a problem. As carbon monoxide related deaths increased during the 1990s, audible alarms became standard.

The alarm points on carbon monoxide detectors are not a simple alarm level (as in smoke detectors) but are a concentration-time function. At lower concentrations (e.g. 100 parts per million) the detector will not sound an alarm for many tens of minutes. At 400 parts per million (PPM), the alarm will sound within a few minutes. This concentration-time function is intended to mimic the uptake of carbon monoxide in the body while also preventing false alarms due to relatively common sources of carbon monoxide such as cigarette smoke.

There are four types of sensors available and they vary in cost, accuracy and speed of response.[12] The latter three types include sensor elements that typically last up to 10 years. At least one CO detector is available which includes a battery and sensor in a replaceable module. Most CO detectors do not have replaceable sensors.

Opto-Chemical

The detector consists of a pad of a coloured chemical which changes colour upon reaction with carbon monoxide. They only provide a qualitative warning of the gas however. The main advantage of these detectors is that they are the lowest cost, but the downside is that they also offer the lowest level of protection.

Biomimetic

A biomimetic (Biotechnology based sensor using cyclodetrins and a chromophore and a number of metal salts) sensor works in a fashion similar to hemoglobin which darkens in the presence of CO proportional to the amount of carbon monoxide in the surrounding environment. This can either be seen directly or connected to a an infrared source of photons such as an IR LED and then monitored using a photodiode. Battery lifespan usually lasts 2–3 years with conventional alkaline, but a lithium battery will last the life of the product. The biotechnology based sensors have a useful operational life of 6 years. These products were the first to enter the mass market, but because they cost more than other sensors they are mostly used in higher-end areas and RVs. The technology has been improved and is the most reliable technology, according to a report from Lawrence Berkeley National Laboratory (LBNL Report 40566). The technology is the only one tested false alarm free and is preferred by those with larger facilties like hospitals, hotels and apartments that use air fresheners, alcohols and other disinfectants where the cost of one false alarm is very high. This technology was invented in the USA and is manufactured in California.

Electrochemical

This is a type of fuel cell that instead of being designed to produce power, is designed to produce a current that is precisely related to the amount of the target gas (in this case carbon monoxide) in the atmosphere. Measurement of the current gives a measure of the concentration of carbon monoxide in the atmosphere. Essentially the electrochemical cell consists of a container, 2 electrodes, connection wires and an electrolyte - typically sulfuric acid. Carbon monoxide is oxidized at one electrode to carbon dioxide while oxygen is consumed at the other electrode. For carbon monoxide detection, the electrochemical cell has advantages over other technologies in that it has a highly accurate and linear output to carbon monoxide concentration, requires minimal power as it is operated at room temperature, and has a long lifetime (typically commercial available cells now have lifetimes of 5 years or greater). Until recently, the cost of these cells and concerns about their long term reliability had limited uptake of this technology in the marketplace, although these concerns are now largely overcome. This technology is now the dominant technology in USA and Europe.

Semiconductor

Thin wires of the semiconductor tin dioxide on an insulating ceramic base provide a sensor monitored by an integrated circuit. This sensing element needs to be heated to approximately 400 deg C in order to operate. Oxygen increases resistance of the tin dioxide, but carbon monoxide reduces resistance therefore by measurement of the resistance of the sensing element means a monitor can be made to trigger an alarm. The power demands of this sensor means that these devices can only be mains powered although a pulsed sensor is now available that has a limited lifetime (months) as a battery powered detector. Device usually lasts on the average of 5–10 years. This technology has traditionally found high utility in Japan and the far east with some market penetration in USA. However the superior performance of electrochemical cell technology is beginning to displace this technology

Digital

Although all home detectors use an audible alarm signal as the primary indicator, some versions also offer a digital readout of the CO concentration, in parts per million. Typically, they can display both the current reading and a peak reading from memory of the highest level measured over a period of time. These advanced models cost somewhat more but are otherwise similar to the basic models.

The digital models offer the advantage of being able to observe levels that are below the alarm threshold, learn about levels that may have occurred during an absence, and assess the degree of hazard if the alarm sounds. They may also aid emergency responders in evaluating the level of past or ongoing exposure or danger.

Portable

Portable CO detectors are also available, these are typically used for professional applications or in some cases by consumers such as property managers for maintenance and diagnosis issues (i.e. sourcing a CO leak). Most offer real time measurements of CO down to a few ppm (usually shown on a digital display), and are more expensive than home safety CO detectors (e.g. ~$250 vs $25). Although Kidde & First Alert dominate the home detector market, there are several manufacturers of portable detectors, such as KWJ Engineering (Pocket CO), Quantum Group, Bacharach, Drager, Industrial Scientific, Fluke, RKI, Sensorcon, and Zellweiger. There are two types of portable detectors, one that is designed for aircraft, cars and trucks. They will warn the driver and passenger if there is a CO hazard. Another type is used by occupational hygenists and first reponders. Digital, fast responsing portable type CO detectors are usually a better choice for real time "on the go" applications as they respond to low levels of CO in seconds rather than minutes or hours (which is the case for UL2034 listed residential alarm).

Wireless

Wireless home safety solutions are available that link carbon monoxide detectors to vibrating pillow pads, strobes or a remote warning handset. This allows those with impediments such as hard of hearing, partially sighted, heavy sleepers or the infirm the precious minutes to wake up and get out in the event of carbon monoxide in their property.

Legislation in the United States

House builders in Colorado are required to install carbon monoxide detectors in new homes in a bill signed into law in March 2009 by the state legislature.

House Bill 1091 requires installation of the detectors in new and resold homes near bedrooms as well as rented apartments and homes. It took effect on July 1, 2009. The legislation was introduced after the death of Denver investment banker Parker Lofgren and his family. Lofgren, 39; his wife Caroline, 42; and their children, Owen, 10, and Sophie, 8, were found dead in a multimillion-dollar home near Aspen, Colorado on Nov. 27, 2008, victims of carbon-monoxide poisoning.

In New York State, "Amanda's Law" (A6093A/C.367) requires one- and two-family residences which have fuel burning appliances to have at least one carbon monoxide alarm installed on the lowest story having a sleeping area, effective since February 22, 2010. Although homes built before Jan. 1, 2008 are allowed to have battery-powered alarms, homes built after that date need to have hard-wired alarms. In addition, New York State contractors have to install a carbon monoxide detector when replacing a fuel burning water heater or furnace if the home is without an alarm. The law is named for Amanda Hansen, a teenager who died from carbon monoxide poisoning from a defective boiler while at a sleepover at a friend's house.[13]

In July 2011, California will require installation of carbon monoxide detectors in existing single-family homes, with multifamily homes following in 2013.[14]

References

  1. ^ Underwriters Laboratories, Protect Your Family from the ‘Silent Killer', http://www.ul.com/global/eng/pages/offerings/perspectives/consumer/stories/carbonmonoxide/, retrieved 2009-09-24 
  2. ^ NFPA 720: Standard for the Installation of Household Carbon Monoxide (CO) Warning Equipment, 2005 Edition, Annex B Dangers of Carbon Monoxide, B.1 Carbon Monoxide, Table B.1 Symptoms of Carbon Monoxide Exposure Based on Concentration
  3. ^ U.S. Consumer Product Safety Commission, Carbon Monoxide Detectors Can Save Lives (CPSC Document #5010), http://www.cpsc.gov/CPSCPUB/PUBS/5010.html, retrieved 2007-07-29 
  4. ^ Metropolitan Utilities District, Carbon monoxide detectors, http://www.mudomaha.com/naturalgas/COdetect.html, retrieved 2007-07-29 
  5. ^ CO Alert, Placement of Carbon Monoxide Detectors Important, http://homesafe.com/coalert/detect.php, retrieved 2009-01-11 
  6. ^ Guyton A C: Medical Physiology 12ed. 2010, page 502
  7. ^ http://www.ncsl.org/programs/environ/envHealth/carbonmonostats07.htm, retrieved on 2009-01-28
  8. ^ http://www.kidde.com/utcfs/Templates/Pages/Template-66/0,8070,pageId%3D4641%26siteId%3D384,00.html, retrieved on 2010-03-14
  9. ^ NFPA 720: Standard for the Installation of Household Carbon Monoxide (CO) Warning Equipment, 2005 Edition
  10. ^ 2009 International Residential Code® for One- and Two-family Dwellings
  11. ^ "Top 5 Things to Know About CO," LifeSafety magazine, Fall 2006
  12. ^ Guide to Prevent Carbon Monoxide Poisoning, http://www.carbon-monoxide-poisoning.com/silent-killer.html, retrieved 2007-07-29 
  13. ^ "Welcome Page". New York State Office of Fire Prevention & Control. http://www.dos.state.ny.us/fire/firewww.html. Retrieved 2010-03-18. 
  14. ^ Senate Bill 183

15. Laura A. Gundel, Michael G. Apte and Albert R. Nematollahi, "Carbon Monoxide Detector Technology Comparison: Response to Various Gases, Lawrence Berkeley National Laboratory (LBNL) Report 40566

External links


Wikimedia Foundation. 2010.

Игры ⚽ Поможем написать реферат

Look at other dictionaries:

  • Carbon monoxide poisoning — This article is about carbon monoxide poisoning. For general information on carbon monoxide, see carbon monoxide. Carbon monoxide poisoning Classification and external resources Spacefilling model of a carbon monoxide molecule …   Wikipedia

  • Carbon monoxide — chembox Name = Carbon monoxide ImageFileL1 = Carbon monoxide 2D.svg ImageSizeL1 = 100px ImageNameL1 = Structure of the carbon monoxide molecule ImageFileR1 = Carbon monoxide 3D vdW.png ImageSizeR1 = 120px ImageNameR1 = Space filling model of the… …   Wikipedia

  • Carbon monoxide poisoning — Poisoning with carbon monoxide, a tasteless odorless gas that is a byproduct of combustion. Carbon monoxide acts as a poison by competing with oxygen for binding sites on hemoglobin, the molecule in red blood cells that carries oxygen from the… …   Medical dictionary

  • Heat detector — A heat detector is a device that responds to changes in ambient temperature. Typically, if the ambient temperature rises above a predetermined threshold an alarm signal is triggered. In the case of sprinkler systems, water will be released to… …   Wikipedia

  • Aspirated smoke detector — An aspirating smoke detector is a type of smoke detector, based on a nephelometer that is capable of detecting the presence of microscopic particles of combustion also known as (smoke) suspended in air by detecting the light scattered from the… …   Wikipedia

  • Smoke detector — A smoke detector is a device that detects smoke, typically as an indicator of fire. Commercial, industrial, and mass residential devices issue a signal to a fire alarm system, while household detectors, known as smoke alarms, generally issue a… …   Wikipedia

  • flame ionization detector — (FID)    A nearly universal gas chromatographic detector. It responds to almost all organic compound. An FID does not respond to nitrogen, hydrogen, helium, oxygen, carbon monoxide or water. This detector ionizes compounds as they reach the end… …   Forensic science glossary

  • Glossary of fuel cell terms — The Glossary of fuel cell terms lists the definitions of many terms used within the fuel cell industry. The terms in this glossary may be used by fuel cell industry associations, in education material and fuel cell codes and standards to name but …   Wikipedia

  • List of sensors — * Accelerometer * Touch sensor * Active pixel sensor * Air flow meter * Alarm sensor * Bedwetting alarm * Bhangmeter * Biochip * Biosensor * Breathalyzer * Capacitance probe * Carbon paste electrode * Carbon monoxide detector * Catadioptric… …   Wikipedia

  • Emerson Radio — Infobox Company company name = Emerson Radio Corporation company company type = Public (amex|MSN) company slogan = We re Playing Your Tune foundation = 1948 location = Parsippany, NJ, USA key people = Adrian Ma, CEO industry = Wholesaler products …   Wikipedia

Share the article and excerpts

Direct link
Do a right-click on the link above
and select “Copy Link”