Condensate pump

Condensate pump

A condensate pump is a specific type of pump used to pump the condensate (water) produced in an HVAC (heating or cooling), refrigeration, condensing boiler furnace or steam system. They may be used to pump the condensate produced from latent water vapor in any of the following gas mixtures:

  • Conditioned (cooled or heated) building air
  • Refrigerated air in cooling and freezing systems
  • Steam in heat exchangers and radiators
  • The exhaust stream of very-high-efficiency furnaces

Condensate recovery systems help you reduce three tangible costs of producing steam:

  • Fuel/energy costs
  • Boiler water make-up and sewage treatment
  • Boiler water chemical treatment

Construction and operation

Condensate pumps as used in hydronic systems are usually electrically powered centrifugal pumps. As used in homes and individual heat exchangers, they are often small and rated at a fraction of a horsepower, but in commercial applications they range in size up to many horsepower and the electric motor is usually separated from the pump body by some form of mechanical coupling. Large industrial pumps may also serve as the feedwater pump for returning the condensate under pressure to a boiler.

Condensate pumps usually run intermittently and have a tank in which condensate can accumulate. Eventually, the accumulating liquid raises a float switch energizing the pump. The pump then runs until the level of liquid in the tank is substantially lowered. Some pumps contain a two-stage switch. As liquid rises to the trigger point of the first stage, the pump is activated. If the liquid continues to rise (perhaps because the pump has failed or its discharge is blocked), the second stage will be triggered. This stage may switch off the HVAC equipment (preventing the production of further condensate), trigger an alarm, or both.

Some systems may include two pumps to service the tank. In this case, the two pumps often alternate operation, and a two-stage switch serves to energize the on-duty pump at the first stage and then energize the remaining pump at the second stage. This second stage action is in addition to any triggering of other system changes as noted for a single pump installation. In this way pump runtime is shared between the two, and a backup pump is provided in case one pump fails to function as designed.

Small pumps have tanks that range from 2 to 4 litres (0.5 to 1 gallon) and are usually supported using the flanges on their tanks or simply placed upon the floor. A plastic impeller in a molded volute at the bottom of the pump provides the pumping action; this impeller is connected to the motor via a metal shaft that extends downwards from the motor mounted above the tank's top. Large pumps are usually pad-mounted drawing liquid from a tank (sump) below the floor. The smallest pumps may have no tank at all and are simply placed within a container such as the drip pan of a dehumidifier appliance.

In industrial steam systems the condensate pump is used to collect and return condensate from remote areas of the plant. The steam produced in the boiler can heat equipment and processes a considerable distance away. Once steam is used it turns to hot water or condensate. This pump and possibly many more around the plant returns this hot water back to a make-up tank closer to the boiler, where it can be reclaimed, chemically treated, and reused, in the boiler, consequently it can sometimes be referred to as a condensate return pump.

In a steam power plant, particularly shipboard ones, the condensate pump is normally located adjacent to the main condenser hotwell often directly below it. This pump sends the water to a make-up tank closer to the steam generator or boiler. If the tank is also designed to remove dissolved oxygen from the condensate, it is known as a Deareating feed tank (DFT). The output of the DFT supplies the feed booster pump which, in turn, supplies the feed pump (feedwater pump) which returns the feedwater to the boiler so the cycle can start over. Two pumps in succession are used to provide sufficient Net Positive Suction Head to prevent cavitation and the subsequent damage associated with it.

This pump is usually associated with a much larger tank, float switch, and an electric motor than the example above. Some systems are so remote that steam power is used to return the condensate where electricity is impractical to provide.

The output of small condensate pumps is usually routed to a sewer, drain, or the outside world via PVCl plastic tubing. If the outlet of the line is at a higher level than the tank of the pump, a check valve is often fitted at the outlet of the pump so that liquid cannot flow backwards into the pump's tank. If the outlet is below the tank level, siphonage usually naturally clears the output line of all liquid when the pump is deenergized. In cold regions of the world, it is important that condensate lines that are exhausted outside be carefully designed so that no water can remain in the line to freeze up; this would block the line from further operation.

Condensate is not pure water. If it is being condensed from an air stream, it may have dust, microbes, or other contaminants in it. If it is condensed from steam, it may have traces of the various boiler water treatment chemicals. And if it is condensed from furnace exhaust gases, it may be acidic, containing sulfuric acid or nitric acid as a result of sulfur and nitrogen dioxides in the exhaust gas stream. Steam and exhaust condensate is usually hot. These various factors may combine (along with local regulations) to require careful handling or even treatment of the condensate and condensate pumps used for these services must be appropriately designed.

External links

Types of Condensate Recovery

Understanding and Solving Equipment Stall


Wikimedia Foundation. 2010.

Игры ⚽ Нужно решить контрольную?

Look at other dictionaries:

  • condensate pump — kondensato siurblys statusas T sritis Energetika apibrėžtis Siurblys, skirtas kondensatui iš kondensatoriaus pašalinti. Šiluminėje arba atominėje elektrinėje šis siurblys kondensatą tiekia į mažo slėgio šildytuvus ir deaeratorių. atitikmenys:… …   Aiškinamasis šiluminės ir branduolinės technikos terminų žodynas

  • condensate pump — Device to remove water condensate that collects beneath an evaporator …   Dictionary of automotive terms

  • Pump — For information on Wikipedia project related discussions, see . A pump is a device used to move gases, liquids or slurries. A pump moves liquids or gases from lower pressure to higher pressure, and overcomes this difference in pressure by adding… …   Wikipedia

  • Boiler feedwater pump — A boiler feedwater pump is a specific type of pump used to pump feedwater into a steam boiler. The water may be freshly supplied or returning condensate produced as a result of the condensation of the steam produced by the boiler. These pumps are …   Wikipedia

  • Bose–Einstein condensate — A Bose–Einstein condensate (BEC) is a state of matter of bosons confined in an external potential and cooled to temperatures very near to absolute zero (val|0|u=K, val| 273.15|u=°C, or val| 459.67|u=°F ). Under such supercooled conditions, a… …   Wikipedia

  • Sorption pump — The sorption pump is a vacuum pump that creates a vacuum by adsorbing molecules on a very porous material like molecular sieve which is cooled by a cryogen, typically liquid nitrogen. The ultimate pressure is about 10 2 mbar. With special… …   Wikipedia

  • Deareating feed tank — A Deaerating Feed Tank (DFT), often found in steam plants that propel ships, is located after the main condensate pump and before the main feed booster pump. From the theoretical Rankine cycle diagram, there are four main processes, or steps: 1… …   Wikipedia

  • Thermal power station — Republika Power Plant, a thermal power station in Pernik, Bulgaria …   Wikipedia

  • Dehumidifier — Typical portable dehumidifier, mounted on casters A dehumidifier is typically a household appliance that reduces the level of humidity in the air, usually for health reasons. Humid air can cause mold and mildew to grow inside homes, which pose… …   Wikipedia

  • Ocean thermal energy conversion — Temperature differences between the surface and 1000m depth in the oceans Ocean Thermal Energy Conversion (OTEC) uses the difference between cooler deep and warmer shallow or surface ocean waters to run a heat engine and produce useful work,… …   Wikipedia

Share the article and excerpts

Direct link
Do a right-click on the link above
and select “Copy Link”