Electrical conduit

Electrical conduit
Electrical conduit risers, seen inside fire-resistance rated shaft, as seen entering bottom of a firestop. The firestop is made of firestop mortar on top, rockwool on the bottom. Raceways are used to protect cables from damage.
Conduit embedded into concrete structure for distribution of cables throughout this highrise apartment building in Mississauga, Ontario, Canada.
Electrical conduit and bus duct in a building at Texaco Nanticoke refinery in Nanticoke, Ontario, 1980s.

An electrical conduit is an electrical piping system used for protection and routing of electrical wiring. Electrical conduit may be made of metal, plastic, fiber, or fired clay. Flexible conduit is available for special purposes.

Conduit is generally installed by electricians at the site of installation of electrical equipment. Its use, form, and installation details are often specified by wiring regulations, such as the US National Electrical Code (NEC) or other national or local code. The term "conduit" is commonly used by electricians to describe any system that contains electrical conductors, but the term has a more restrictive definition when used in wiring regulations.

Some early electric lighting installations made use of existing gas pipe to gas light fixtures which had been converted to electric lamps. Since this technique provided very good mechanical protection for interior wiring, it was extended to all types of interior wiring and by the early 20th century purpose-built couplings and fittings were manufactured for electrical use.

Contents

Comparison with other wiring methods

Electrical conduit provides very good protection to enclosed conductors from impact, moisture, and chemical vapors. Varying numbers, sizes, and types of conductors can be pulled into a conduit, which simplifies design and construction compared to multiple runs of cables or the expense of customised composite cable. Wiring systems in buildings may be subject to frequent alterations. Frequent wiring changes are made simpler and safer through the use of electrical conduit, as existing conductors can be withdrawn and new conductors installed, with little disruption along the path of the conduit. A conduit system can be made waterproof or submersible. Metal conduit can be used to shield sensitive circuits from electromagnetic interference, and also can prevent emission of such interference from enclosed power cables.

When installed with proper sealing fittings, a conduit will not permit the flow of flammable gases and vapors, which provides protection from fire and explosion hazard in areas handling volatile substances.

Some types of conduit are approved for direct encasement in concrete. This is commonly used in commercial buildings to allow electrical and communication outlets to be installed in the middle of large open areas. For example, retail display cases and open-office areas use floor-mounted conduit boxes to connect power and communications cables.

Both metal and plastic conduit can be bent at the job site to allow a neat installation without excessive numbers of manufactured fittings. This is particularly advantageous when following irregular or curved building profiles.

The cost of conduit installation is higher than other wiring methods due to the cost of materials and labor. In applications such as residential construction, the high degree of physical damage protection is not required so the expense of conduit is not warranted. Conductors installed within conduit cannot dissipate heat as readily as those installed in open wiring, so the current capacity of each conductor must be reduced if many are installed in one conduit. It is impractical, and prohibited by wiring regulations, to have more than 360 degrees of total bends in a run of conduit, so special outlet fittings must be provided to allow conductors to be installed without damage in such runs. While metal conduit can be used as a grounding conductor, the circuit length is limited. A long run of conduit as grounding conductor will not allow proper operation of overcurrent devices on a fault, for example.

Types of conduit

Conduit systems are classified by the wall thickness, mechanical stiffness, and material used to make the tubing.

Rigid Metal Conduit (RMC)

Rigid Metal Conduit (RMC) is a thick threaded tubing, usually made of coated steel, stainless steel or aluminum.

Rigid Nonmetallic Conduit (RNMC)

Rigid Nonmetallic Conduit (RNMC) is a non-metallic unthreaded tubing.

Galvanized rigid conduit (GRC)

Galvanized rigid conduit (GRC) is galvanized steel tubing, with a tubing wall that is thick enough to allow it to be threaded. Its common applications are in commercial and industrial construction. [1]

Electrical metallic tubing (EMT)

Electrical metallic tubing (EMT), sometimes called thin-wall, is commonly used instead of galvanized rigid conduit (GRC), as it is less costly and lighter than GRC. EMT itself may not be threaded, but can be used with threaded fittings that clamp to it. Lengths of conduit are connected to each other and to equipment with clamp-type fittings. Like GRC, EMT is more common in commercial and industrial buildings than in residential applications. EMT is generally made of coated steel, though it may be aluminum.

Electrical Nonmetallic Tubing (ENT)

Electrical Nonmetallic Tubing (ENT) is a thin-walled corrugated tubing that is moisture-resistant and flame retardant. It is pliable such that it can be bent by hand and is often flexible although the fittings are not. It is not threaded due to its corrugated shape although the fittings might be.

Flexible Metallic Conduit (FMC)

Flexible metallic conduit used in an underground parking facility.

Flexible Metallic Conduit (FMC, often informally called greenfield or flex) is made by the helical coiling of a self-interlocked ribbed strip of aluminum or steel, forming a hollow tube through which wires can be pulled. FMC is used primarily in dry areas where it would be impractical to install EMT or other non-flexible conduit, yet where metallic strength to protect conductors is still required. The flexible tubing does not maintain any permanent bend.

FMC may be used as an equipment grounding conductor if specific provisions are met regarding the trade size and length of FMC used in addition to the amperage of the circuits contained in the conduit. In general an equipment grounding conductor must be pulled through the FMC with an ampacity suitable to carry the fault current likely imposed on the largest circuit contained within the FMC.

Liquidtight Flexible Metal Conduit (LFMC)

Liquidtight Flexible Metal Conduit (LFMC) is a metallic flexible conduit covered by a waterproof plastic coating. The interior is similar to FMC.

Flexible Metallic Tubing (FMT)

Flexible Metallic Tubing (FMT) is not the same as Flexible Metallic Conduit (FMC) which is described in National Electrical Code (NEC) Article 348. FMT is a raceway, but not a conduit and is described in a separate NEC Article 360. It only comes in 1/2" & 3/4" trade sizes, whereas FMC is sized 1/2" ~ 4" trade sizes. NEC 360.2 describes it as: "A raceway that is circular in cross section, flexible, metallic and liquidtight without a nonmetallic jacket."

Liquidtight Flexible Nonmetallic Conduit (LFNC)

Liquidtight Flexible Nonmetallic Conduit (LFNC) refers to several types of flame-resistant non-metallic tubing. Interior surfaces may be smooth or corrugated. There may be integral reinforcement within the conduit wall. It is also known as FNMC.

Aluminum conduit

Aluminum conduit, similar to galvanized steel conduit, is a rigid conduit, generally used in commercial and industrial applications, where a higher resistance to corrosion is needed. Such locations would include food processing plants, where large amounts of water and cleaning chemicals would make galvanized conduit unsuitable. Aluminum cannot be directly embedded in concrete, since the metal reacts with the alkalis in cement. The conduit may be coated to prevent corrosion by incidental contact with concrete. The extra cost of aluminum is somewhat offset by the lower labor cost to install, since a length of aluminum conduit will have about one-third the weight of an equally-sized rigid steel conduit.

Intermediate metal conduit (IMC)

Intermediate Metal Conduit (IMC) is a steel tubing heavier than EMT but lighter than RMC. It may be threaded.

PVC conduit

PVC conduit is the lightest in weight compared to other conduit materials, and usually lower in cost than other forms of conduit. In North American electrical practice, it is available in three different wall thicknesses, with the thin-wall variety only suitable for embedded use in concrete, and heavier grades suitable for direct burial and exposed work. The various fittings made for metal conduit are also made for PVC. The plastic material resists moisture and many corrosive substances, but since the tubing is non-conductive an extra bonding (grounding) conductor must be pulled into each conduit. PVC conduit may be heated and bent in the field. Joints to fittings are made with slip-on solvent-welded connections,which set up rapidly after assembly and attain full strength in about one day. Since slip-fit sections do not need to be rotated during assembly, the special union fittings used with threaded conduit (Ericson) are not required. Since PVC conduit has a higher thermal coefficient of expansion than other types, it must be mounted so as to allow for expansion and contraction of each run. Care should be taken when installing PVC underground in multiple or parallel run configurations due to mutual heating effect of cable

Plastic tubing for use as electrical conduit.

Other metal conduits

In extreme corrosion environments where plastic coating of the tubing is insufficient, conduits may be made from stainless steel, bronze or brass.

Underground conduit

Conduit may be installed underground between buildings, structures, or devices to allow installation of power and communication cables. An assembly of these conduits, often called a duct bank, may either be directly buried in earth or encased in concrete (sometimes with refinforcing rebar to aid against shear). A duct bank will allow replacement of damaged cables between buildings or additional power and communications circuits to be added, without the expense of re-excavation of a trench. While metal conduit is occasionally used for burial, usually PVC, polyethylene or polystyrene plastics are now used due to lower cost and easier installation.

Formerly, compressed asbestos fiber mixed with cement (such as Transite) was used for some underground installations. Telephone and communications circuits were typically installed in fired-clay conduit.

Cost comparison of some types of conduit

Cost relative to Rigid Galvanized Steel (RGS) conduit, 3/4 inch (21 metric) size
Relative RGS Aluminum IMC EMT PVC
Labor 1.0 0.89 0.89 0.62 0.55
Weight 1.0 0.34 0.76 0.42 0.20
Material cost 1.0 0.99 0.84 0.35 0.43

Exact ratios of installation labor, weight and material cost vary depending on the size of conduit, but the values for 3/4 inch (21 metric) trade size are representative. [2]

Fittings

Despite the similarity to pipes used in plumbing, purpose-designed fittings are used to connect conduit.

Box connectors join conduit to a junction box or other electrical box. A typical box connector is inserted into a knockout in a junction box, with the threaded end then being secured with a ring (called a lock nut) from within the box, as a bolt would be secured by a nut. The other end of the fitting usually has a screw or compression ring which is tightened down onto the inserted conduit. Fittings for non-threaded conduits are either secured with set screws or with a compression nut that encircles the conduit. Fittings for general purpose use with metal conduits may be made of die-cast zinc, but where stronger fittings are needed, they are made of copper-free aluminum or cast iron.

Couplings connect two pieces of conduit together.

Sometimes the fittings are considered sufficiently conductive to bond (electrically unite) the metal conduit to a metal junction box (thus sharing the box's ground connection); other times, grounding bushings are used which have bonding jumpers from the bushing to a grounding screw on the box.[3]

Unlike water piping, if it the conduit is to be watertight, the idea is to keep water out, not in. In this case, gaskets are used with special fittings, such as the weatherhead leading from the overhead electrical mains to the electric meter.

Flexible metal conduit usually uses fittings with a clamp on the outside of the box, just like bare cables would.

Conduit bodies

A conduit body can be used to provide pulling access in a run of conduit, to allow more bends to be made in a particular section of conduit, to make connections if the conduit body is rated for such use, to conserve space where a full size bend radius would be impractical or impossible, or to split a conduit path into multiple directions. Conduit bodies differ from junction boxes in that they are not required to be individually supported, this makes them very useful in practical applications. Conduit bodies are commonly referred to as condulets, a term trademarked by Cooper Crouse-Hinds company, a division of Cooper Industries.

Conduit bodies come in various types, moisture ratings, and materials, including galvanized steel, aluminum, and PVC. Depending on the material, they use different mechanical methods for securing conduit. Among the types are:

  • L-shaped bodies ("Ells") include the LB, LL, and LR, where the inlet is in line with the access cover and the outlet is on the back, left and right, respectively. In addition to providing access to wires for pulling, "L" fittings allow a 90 degree turn in conduit where there is insufficient space for a full-radius 90 degree sweep (curved conduit section).
  • T-shaped bodies ("Tees") feature an inlet in line with the access cover and outlets to both the cover's left and right.
  • C-shaped bodies ("Cees") have identical openings above and below the access cover, and are used to pull conductors in a straight runs as they make no turn between inlet and outlet.
  • "Service Ell" bodies (SLBs), shorter ells with inlets flush with the access cover, are frequently used where a circuit passes through an exterior wall from outside to inside.

Other wireways

Surface Mounted Raceway (wire molding)

This type of "decorative" conduit is designed to provide an aesthetically acceptable passageway for wiring without hiding it inside or behind a wall. This is used where additional wiring is required, but where going through a wall would be difficult or require remodeling. The conduit has an open face with removable cover, secured to the surface, and wire is placed inside. Plastic raceway is often used for telecommunication wiring, such as network cables in an older structure, where it is not practical to drill through concrete block.

Advantages
  • It allows one to add new wiring to an existing building without removing or cutting holes into the drywall, lath and plaster, concrete, or other wall finish.
  • It allows circuits to be easily locatable and accessible for future changes thus enabling minimum effort upgrades.
Disadvantages
  • Its appearance may not be acceptable to all observers.

Trunking

The term trunking is used in the United Kingdom for electrical wireways, generally rectangular in cross section with removable lids.

Mini Trunking is a term used in the UK for small form-factor (usually 6mm to 25mm square or rectangle sectioned) PVC wireways. [4]

In North American practice "wire trough" or "lay-in wireways" are terms used to designate similar products, but these are never used enclosed in masonry or a wall.

Passive fire protection

Conduit is of relevance to both firestopping, where they become penetrants, and fireproofing, where circuit integrity measures can be applied on the outside to keep the internal cables operational during an accidental fire. The British standard BS476 also considers internal fires, whereby the fireproofing must protect the surroundings from cable fires. Any external treatments must consider the effect upon ampacity derating.

See also

Notes

  1. ^ R.K. Clidero Applications of Electrical Construction, General Publishing Co., Don Mills Ontario Canada, 1975, ISBN 0-7736-5011-3
  2. ^ John H. Chiang, (Ed), RS Means Electrical Cost Data 30th Annual Edition, RSMeans Construction Publishers, Kingston MA USA, 2007, ISBN 0-87629-856-0
  3. ^ Cauldwell 2002:109.
  4. ^ Mini Trunking PVC White 25 x 16mm Pack of 20 - Screwfix.com, Where the Trade Buys

Bibliography

  • Cauldwell, Rex (2002). Wiring a House (For Pros By Pros). Newtown, CT, USA: Taunton Press. ISBN 1-56158-527-0. 

External links


Wikimedia Foundation. 2010.

Игры ⚽ Поможем написать курсовую

Look at other dictionaries:

  • Electrical wiring (United States) — Electrical wiring in general refers to conductors used to carry electricity and their accessories. General aspects of electrical wiring as used to provide power in or to buildings and structures, commonly referred to as building wiring, are… …   Wikipedia

  • Conduit — Contents 1 Common Channels 1.1 In Geography 1.2 In Electrical Systems …   Wikipedia

  • Electrical wiring — in general refers to insulated conductors used to carry electricity, and associated devices. This article describes general aspects of electrical wiring as used to provide power in buildings and structures, commonly referred to as building wiring …   Wikipedia

  • Conduit (comics) — Conduit Conduit as he appears in Adventures of Superman #0. Art by Barry Kitson (pencils) and Glenn Whitmore (colors). Publication information Publisher …   Wikipedia

  • Conduit current collection — Abandoned conduit trackage at the Kingsway Tramway Subway in London Conduit current collection is a system of electric current collection used by electric trams, where the power supply is carried in a channel under the roadway, rather than… …   Wikipedia

  • conduit — [[t]kɒ̱ndjuɪt, AM duɪt[/t]] conduits 1) N COUNT A conduit is a small tunnel, pipe, or channel through which water or electrical wires go. Syn: pipe 2) N COUNT: oft N for/to n A conduit is a person or country that links two or more other people or …   English dictionary

  • electrical components —   ▬▬▬▬▬▬▬▬ Types of electrical components and devices include: adaptor ammeter armature battery bayonet fitting cable ceiling rose circuit breaker conduit continuity tester copper conductor dimmer switch dry cell battery earthed plug electrical… …   Useful english dictionary

  • conduit — con•duit [[t]ˈkɒn dwɪt, du ɪt, dyu ɪt, dɪt[/t]] n. 1) hyd a pipe, tube, or natural channel for conveying water or other fluid 2) a channel through which anything is conveyed: a conduit for information[/ex] 3) elm a structure containing ducts for… …   From formal English to slang

  • conduit — /ˈkɒndʒuət / (say konjoohuht), /ˈkɒndjuət/ (say kondyoohuht), /ˈkɒndɪt / (say kondit) noun 1. a pipe, tube, or the like, for conveying water or other fluid. 2. some similar natural passage. 3. Electricity a pipe that encases electrical wires or… …  

  • conduit — noun a) A pipe or channel for conveying water etc. b) A duct or tube into which electrical cables may be pulled; a type of raceway …   Wiktionary

Share the article and excerpts

Direct link
Do a right-click on the link above
and select “Copy Link”