High voltage

High voltage

The term high voltage characterizes electrical circuits, in which the voltage used is the cause of particular safety concerns and insulation requirements. High voltage is used in electrical power distribution, in cathode ray tubes, to generate X-rays and particle beams, to demonstrate arcing, for ignition, in photomultiplier tubes, and high power amplifier vacuum tubes and other industrial and scientific applications.

Definition

The numerical definition of "high voltage" depends on the context of the discussion. Two factors considered in the classification of a "high voltage" are the possibility of causing a spark in air, and the danger of electric shock by contact or proximity. The definitions may refer either to the voltage between two conductors of a system, or between any conductor and ground.

In electric power transmission engineering, high voltage is usually considered any voltage over approximately 35,000 volts. This is a classification based on the design of apparatus and insulation.

The International Electrotechnical Commission and its national counterparts (IET, IEEE, VDE, etc.) define "high voltage" circuits as those with more than 1000 V for alternating current and at least 1500 V for direct current, and distinguish it from low voltage (50–1000 V AC or 120–1500 V DC) and extra low voltage (<50 V AC or <120 V DC) circuits. This is in the context of building wiring and the safety of electrical apparatus.

In the United States 2005 National Electrical Code (NEC), "high voltage" is any voltage over 600 V (article 490.2). British Standard BS 7671:2008 defines "high voltage" as any voltage difference between conductors that is higher than 1000 V AC or 1500 V ripple-free DC, or any voltage difference between a conductor and Earth that is higher than 600 V AC or 900 V ripple-free DC. Electricians may only be licensed for particular voltage classes, in some jurisdictions. [ One such jurisdiction is Manitoba, where the "Electrician's Licence Act, CCSM E50, establishes classes of electrician's licences by voltage. ] For example an electrical license for a specialized sub-trade such as installation of HVAC systems, fire alarm systems, closed circuit television systems may only be authorized to install systems energized up to 30 volts between conductors, and may not be permitted to work on mains-voltage circuits.

The general public may consider household mains circuits (100–250 V AC), which carry the highest voltages they normally encounter, to be "high voltage".

Voltages over approximately 50 volts can usually cause dangerous amounts of current to flow through a human being touching two points of a circuit, so safety standards generally are more restrictive where the chance of contact with such high voltage circuits exists.

In digital electronics, a "high" voltage is the one that represents a logic 1; this may be only several hundred millivolts for some logic families.

The definition of "extra high voltage" (EHV) depends on the context of the discussion. In electric power transmission engineering this refers to equipment designed for more than 235,000 volts between conductors. In electronics systems, a power supply that provides greater than 275,000 volts is known as an "EHV Power Supply". It is often used in experiments in physics.

The accelerating voltage for a television cathode ray tube may be described as "extra high voltage" or "extra-high tension" (EHT), as compared to other voltage supplies within the equipment. This type of supply ranges from >5 kV to about 50 kV.

afety

Voltages of greater than 50 V applied across dry unbroken human skin are capable of producing heart fibrillation if they produce electric currents in body tissues which happen to pass through the chest area. The electrocution danger is mostly determined by the low conductivity of dry human skin. If skin is wet, or if there are wounds, or if the voltage is applied to electrodes which penetrate the skin, then even voltage sources below 40 V can be lethal if contacted.

Accidental contact with high voltage supplying sufficent energy will usually result in severe injury or death. This can occur as a person's body provides a path for current flow causing tissue damage and heart failure. Other injuries can include burns from the arc generated by the accidental contact. These can be especially dangerous if the victim's airways are affected. Injuries may also be suffered as a result of the physical forces exerted as people may fall from height or be thrown a considerable distance.

Low-energy exposure to high voltage may be harmless, such as the spark produced in a dry climate when touching a doorknob after walking across a carpeted floor.

parks in air

The dielectric breakdown strength of dry air, at Standard Temperature and Pressure (STP), between spherical electrodes is approximately 33 kV/cm. [A. H. Howatson, "An Introduction to Gas Discharges", Pergamom Press, Oxford, 1965, no ISBN - page 67] This is only as a rough guide since the actual breakdown voltage is highly dependent upon the electrode shape and size. Strong electric fields (from high voltages applied to small or pointed conductors), often produce violet-colored corona discharges in air, as well as visible sparks. Voltages below about 500-700 volts cannot produce easily visible sparks or glows in air at atmospheric pressure, so by this rule these voltages are 'low'. However, under conditions of low atmospheric pressure (such as in high-altitude aircraft), or in an environment of noble gas such as argon, neon, etc., sparks will appear at much lower voltages. 500 to 700 volts is not a fixed minimum for producing spark breakdown, but it is a rule of thumb. For air at STP, the minimum sparkover voltage is around 380 volts.

While lower voltages will not generally jump a gap that is present before the voltage is applied, interrupting an existing current flow often produces a low voltage spark or arc. As the contacts are separated, a few small points of contact become the last to separate. The current becomes constricted to these small "hot spots", causing them to become incandescent, so that they emit electrons (through thermionic emission). Even a small 9 V battery can spark noticeably by this mechanism in a darkened room. The ionized air and metal vapour (from the contacts) form plasma, which temporarily bridges the widening gap. If the power supply and load allow sufficient current to flow, a self-sustaining arc may form. Once formed, an arc may be extended to a significant length before breaking the circuit. Attempting to open an inductive circuit often forms an arc since the inductance provides a high voltage pulse whenever the current is interrupted. AC systems make sustained arcing somewhat less likely since the current returns to zero twice per cycle. The arc is extinguished every time the current goes through a zero crossing, and must reignite during the next half cycle in order to maintain the arc.

Unlike an ohmic conductor, the voltage at the ends of an arc decreases as the current increases. This makes unintentional arcs in electrical apparatus dangerous since once even a small arc is initiated, if sufficient current is available, the arc will grow. Such arcs can cause great damage to equipment and present a severe fire hazard. Intentionally produced arcs, such as used in lighting or welding, require some element in the circuit to stabilize the arc's current/voltage characteristics.

Electrostatic devices and phenomena

A high voltage is not necessarily dangerous if it cannot deliver substantial current. The common static electric sparks seen under low-humidity conditions always involve voltage buildups well above 700 V. For example, sparks to car doors in winter can involve voltages as high as 20,000 V [ [http://www.jci.co.uk/Carseats2.html John Chubb, "Control of body voltage getting out of a car," IOP Annual Congress, Brighton, 1998 ] ] . Also, physics demonstration devices such as Van de Graaff generators and Wimshurst machines can produce voltages approaching one million volts, yet at worst they deliver a brief sting. These devices have a limited amount of stored energy, so the current produced is low and usually for a short time. [ [http://www.amasci.com/emotor/vdgdesc.html Van de Graaff Generators Frequently Asked Questions - 1998 William J. Beaty] ] During the discharge, these machines apply high voltage to the body for only a millionth of a second or less. The discharge may involve extremely high power over very short periods, but in order to produce heart fibrillation, an electric power supply must produce a significant current in the heart muscle continuing for many milliseconds, and must deposit a total energy in the range of at least millijoules or higher. Alternatively, it must deliver enough energy to damage tissue through heating. Since the duration of the discharge is brief, it generates far less heat (spread over time) than a mobile phone.

Note that Tesla coils are a special case, and touching them is not recommended. Among other issues, they have a tendency to arc to their own bottom-end circuitry, which can introduce powerline frequency (50 Hz or 60 Hz, and capable in any case of depolarizing cells and stopping the heart) currents at lethally high voltages to the body.

Power lines

Electrical transmission and distribution lines for electric power always use voltages significantly higher than 50 volts, so contact with or close approach to the line conductors presents a danger of electrocution. Contact with overhead wires is a frequent cause of injury or death. Metal ladders, farm equipment, boat masts, construction machinery, aerial antennas, and similar objects are frequently involved in fatal contact with overhead wires. Digging into a buried cable can also be dangerous to workers at an excavation site. Digging equipment (either hand tools or machine driven) that contacts a buried cable may energize piping or the ground in the area, resulting in electrocution of nearby workers. Unauthorized persons climbing on power pylons or electrical apparatus are also frequently the victims of electrocution.National Institute for Occupational Safety and Health FACE - Fatality Assessment and Control Evaluation [http://www.cdc.gov/niosh/injury/traumaelface.html] cases of high voltage related casualties.] At very high transmission voltages even a close approach can be hazardous since the high voltage may spark across a significant air gap.

For high voltage and extra-high voltage transmission lines, specially trained personnel use so-called "live line" techniques to allow hands-on contact with energized equipment. In this case the worker is electrically connected to the high voltage line but thoroughly insulated from the earth so that he is at the same electrical potential as the line. Since training for such operations is lengthy, and still presents a danger to personnel, only very important transmission lines are subject to maintenance while live. Outside these properly engineered situations, it should not be assumed that being insulated from earth guarantees that no current will flow to earth as grounding, or arcing to ground, can occur in unexpected ways, and high-frequency currents can cause burns even to an ungrounded person (touching a transmitting antenna is dangerous for this reason, and a high-frequency Tesla Coil can sustain a spark with only one endpoint).

Protective equipment on high-voltage transmission lines normally prevents formation of an unwanted arc, or ensures that it is quenched within tens of milliseconds. Electrical apparatus which interrupts high-voltage circuits is designed to safely direct the resulting arc so that it dissipates without damage. High voltage circuit breakers often use a blast of high pressure air, a special dielectric gas (such as SF6 under pressure), or immersion in mineral oil to quench the arc when the high voltage circuit is broken.

Arc flash hazard

Depending on the short circuit current available at a switchgear line-up, a hazard is presented to maintenance and operating personnel due to the possibility of a high-intensity electric arc. Maximum temperature of an arc can exceed 10,000 kelvin, and the radiant heat, expanding hot air, and explosive vaporization of metal and insulation material can cause severe injury to unprotected workers. Such switchgear line-ups and high-energy arc sources are commonly present in electric power utility substations and generating stations, industrial plants and large commercial buildings. In the United States the National Fire Protection Association, has published a guideline standard NFPA 70E for evaluating and calculating "arc flash hazard", and provides standards for the protective clothing required for electrical workers exposed to such hazards in the workplace.

Explosion hazard

Even voltages insufficient to break down air can be associated with enough energy to ignite atmospheres containing flammable gases or vapours, or suspended dust. For example hydrogen gas, natural gas, or gasoline vapor mixed with air can be ignited by sparks produced by electrical apparatus. Examples of industrial facilities with hazardous areas are petrochemical refineries, chemical plants, grain elevators, and some kinds of coal mines.

Measures taken to prevent such explosions include:
*Intrinsic safety by the use of apparatus designed not to accumulate enough stored electrical energy to trigger an explosion
*Increased safety, which applies to devices using measures such as oil-filled enclosures to prevent sparks
*Explosion-proof enclosures, which are designed so that an explosion within the enclosure cannot escape and ignite a surrounding explosive atmosphere (this designation does not imply that the apparatus will survive an internal or external explosion).

In recent years standards for explosion hazard protection have become more uniform between European and North American practice. The "zone" system of classification is now used in modified form in U.S. National Electrical Code and in the Canadian electrical code. Intrinsic safety apparatus is now approved for use in North American applications, though the explosion-proof enclosures used in North America are still uncommon in Europe.

Toxic gases

Electrical discharges, including partial discharge and corona, can produce small quantities of toxic gases, which in a confined space can be a serious health hazard. These gases include ozone and various oxides of nitrogen.

Lightning

The largest-scale sparks are those produced naturally by lightning. An average bolt of negative lightning carries a current of 30-to-50 kiloamperes, transfers a charge of 5 coulombs, and dissipates 500 megajoules of energy (enough to light a 100 watt light bulb for 2 months). However, an average bolt of positive lightning (from the top of a thunderstorm) may carry a current of 300-to-500 kiloamperes, transfer a charge of up to 300 coulombs, have a potential difference up to 1 gigavolt (a billion volts), and may dissipate enough energy to light a 100 watt lightbulb for up to 95 years. A negative lightning stroke typically lasts for only tens of microseconds, but multiple strikes are common. A positive lightning stroke is typically a single event. However, the larger peak current may flow for hundreds of milliseconds, making it considerably hotter and more dangerous than negative lightning.

Hazards due to lightning obviously include a direct strike on persons or property. However, lightning can also create dangerous voltage gradients in the earth and can charge extended metal objects such as telephone cables, fences, and pipelines to dangerous voltages that can be carried many miles from the site of the strike. Although many of these objects are not normally conductive, very high voltage can cause the electrical breakdown of such insulators, causing them to act as conductors. These transferred potentials are dangerous to people, livestock, and electronic apparatus. Lightning strikes also start fires and explosions, which result in fatalities, injuries, and property damage. For example, each year in North America, thousands of forest fires are started by lightning strikes.

Measures to control lightning can mitigate the hazard; these include lightning rods, shielding wires, and bonding of electrical and structural parts of buildings to form a continuous enclosure.

Lightning discharges in the atmosphere of Jupiter are thought to be the source of the planet's powerful radio frequency emissions.

ee also

* Electrical engineering
* Electric power transmission (includes a 'Health concerns' section)
* Lock and tag "Safety Procedures" ("As required by OSHA and NFPA 70E in the USA")
* People : Nikola Tesla, Robert J. Van de Graaff, Thomas Burton Kinraide
* Devices : Tesla coil, spark gap
* Other: voltage, 25 kV AC

References

* High Voltage Engineering - Dr M S Naidu & Dr V Kamaraju, Publisher: McGraw-Hill
* [http://www.crcpress.com/shopping_cart/products/product_detail.asp?sku=DK2791&isbn=9780824740566&parent_id=&pc=] Vladimir Gurevich "Protection Devices and Systems for High-Voltage Applications", CRC Press, London - New York, 2003, 292 p.

External links

* [http://www.transportsupport.co.uk/main/products_overhead_cable_detectors.html Prevention of High Voltage Accidents]
* [http://www.nfpa.org/catalog/ "NFPA 70E": Electrical Safety in the Workplace, USA]
* [http://www.mikeholt.com/technical.php?id=nec/technicalnecfreestuff Mike Holt NEC in the USA]
* [http://www.eh.doe.gov/techstds/standard/hdbk1092/hdbk1092.pdf USA Department of Energy "electrical safety handbook"]
* [http://www.highvoltageinfo.com/glossary.php High voltage glossary]
* [http://www.crcpress.com/shopping_cart/products/product_detail.asp?sku=DK2791&isbn=9780824740566&parent_id=&pc=] Vladimir Gurevich "Protection Devices and Systems for High Voltage Applications", CRC Press, London - New York, 2003, 292 p.


Wikimedia Foundation. 2010.

Игры ⚽ Нужно сделать НИР?

Look at other dictionaries:

  • High Voltage — Студийный альбом AC/DC Дата выпуска 14 мая 1976 Записан …   Википедия

  • High Voltage — (1975) Álbum de estudio de AC⚡DC Publicación Febrero 17 de 1975 (sólo Australia) Grabación Noviembre 1974 Albert Studios, Sydney Género(s) Hard rock, blues rock, rock and roll …   Wikipedia Español

  • High Voltage — (Australien) Studioalbum von Veröffentlichung 17. Februar 1975 …   Deutsch Wikipedia

  • High voltage — est le premier album du groupe australien AC/DC. Cet album est sorti le 17 février 1975 en Australie. Une version est publiée en 1976 pour l Europe et les États Unis reprenant leurs deux premiers albums (2 chansons viennent de High… …   Wikipédia en Français

  • high-voltage — adj. 1. having, operating on, or powered by high voltage; as, a high voltage generator; a high voltage line. Syn: high tension. [WordNet 1.5] 2. same as {high powered}. Syn: high octane, high powered, high power. [WordNet 1.5] …   The Collaborative International Dictionary of English

  • high voltage — high tension, operating under a high voltage …   English contemporary dictionary

  • high-voltage — adjective 1. vigorously energetic or forceful a high octane sales manager a high octane marketing plan high powered executives a high voltage theatrical entrepreneur • Syn: ↑high octane, ↑high powered, ↑high power, ↑ …   Useful english dictionary

  • High Voltage —  Ne pas confondre avec la version australienne. High Voltage Album par AC/DC Sortie 14 mai 1976 Enregistrement …   Wikipédia en Français

  • high-voltage — /huy vohl tij/, adj. 1. operating on or powered by high voltage: a high voltage generator. 2. Informal. dynamic; powerful: a high voltage theatrical entrepreneur. [1965 70] * * * …   Universalium

  • high voltage — aukštoji įtampa statusas T sritis automatika atitikmenys: angl. high tension; high voltage vok. Hochspannung, f rus. высокое напряжение, n pranc. haute tension, f …   Automatikos terminų žodynas

Share the article and excerpts

Direct link
Do a right-click on the link above
and select “Copy Link”