Overhead line crossing

Overhead line crossing

An overhead line crossing is the crossing of an obstacle—such as a traffic route, a river, a valley or a strait—by an overhead power line. The style of crossing depends on the local conditions and regulations at the time the power line is constructed. Overhead line crossings can sometimes require extensive construction and can also have operational issues. In such cases, those in charge of construction should consider whether a crossing of the obstacle would be better accomplished by an underground or submarine cable.

Contents

Crossings of roads and railway lines

Overhead line crossings of roads, railway lines, and small- and medium-sized watercourses do not normally require special construction. However, a former law in Germany for crossing dictated that there must be an anchor pylon on each side of a crossing of the national railway, which can be seen on some old power lines. For overhead line crossings of motorways the pylons must be rebuilt before they wear out, because these demand additional maintenance. If local conditions are appropriate, an overhead line can be implemented by way of a valley bridge. For example, the Koersch valley bridge near Esslingen, Germany carries the 110 kV, three-phase line of the EnBW AG with 2 circuits. Because of the danger of short circuits from falling objects, undercrossings are typically avoided.

Crossings of overhead lines at state borders

380 kV-powerline crossing the national border between Bavaria and Czech near Waidhaus. The pylon in the foreground stands in Bavaria the others are in Czech

There is frequently an anchor pylon on each side of the border, particularly if the lines on either side of the border are operated by different companies. This setup reduces maintenance work, which would otherwise require direct coordination of workers on both sides of the border, and avoids possible authority problems associated with border crossings as much as possible.

Crossings of other overhead lines

The only crossing of two different HVDC overhead powerlines in the Western hemisphere, CU and Square Butte in North Dakota

At crossings of overhead lines by other overhead lines, the two lines must be kept at the necessary safety distances between the lines and the ground. As a rule, the line with the lower voltage passes under the line with higher voltage. Construction workers try to plan these crossings in such a way that their construction is as economical as possible. This is usually done by leaving unchanged the line that is crossed, if possible. Undercrossings of existing lines are often constructed in proximity to the line's pylons, since this can often be accomplished without raising the existing pylons and while keeping the necessary safety distances between the ground and the other line.

In the course of undercrossings the pylon picture is frequently changed, and because of its small height it is preferable to create an arrangement with conductors in one level. Sometimes at such crossings there can be problems because of the maximum pylon height allowed for flight safety reasons. If it is not possible at a given location for the pylons of the upper line to be built at a necessary height, the line running below it will be rebuilt on smaller pylons or replaced with an underground cable.

A unique[citation needed] undercrossing of two powerlines can be found north of Kincardine at Scotland at 56°5'17"N 3°43'11"W. Here crosses the powerline Kincardine-Tealing two other lines. One of the two circuits of Kincardine-Tealing powerline crosses these lines on two small pylons and the other circuit via an underground cable.

Special crossings from overhead lines of other overhead lines

There are some crossings between two overhead powerlines, which are unique, either as both lines are of special type or the unique way of implemention

Coordinates Line 1 Line 2 Reason of unity
56°2′26″N 3°53′20″W / 56.04056°N 3.88889°W / 56.04056; -3.88889 (Powerline Longannet Power Station - Glasgow,Bishopbridge crosses powerline Longannet Power Station - Glasgow,Carmyle) Longannet Power Station - Glasgow,Carmyle Longannet Power Station - Glasgow,Bishopbridge Powerline Longannet Power Station - Glasgow,Bishopbridge crosses powerline Longannet Power Station - Glasgow,Carmyle as underground cable
56°5′17″N 3°43′11″W / 56.08806°N 3.71972°W / 56.08806; -3.71972 (Powerline Kincardine - Tealing crosses powerlines Longannet Power Station - Glasgow,Carmyle, Longannet Power Station - Glasgow,Bishopbridge) Longannet Power Station - Glasgow,Carmyle, Longannet Power Station - Glasgow,Bishopbridge Kincardine - Tealing one circuit of double-circuit line crosses two powerlines as underground cable
47°02′48″N 100°05′49″W / 47.04667°N 100.09694°W / 47.04667; -100.09694 (CU crosses Square Butte) CU (Coal Creek Power Station - Rockford, Minnesota) Square Butte (Center, North Dakota - Adolph, Minnesota) only crossing of 2 HVDC powerlines outside China
48°44′1″N 38°43′26″E / 48.73361°N 38.72389°E / 48.73361; 38.72389 (HVDC Volgograd-Donbass crosses its electrode line) HVDC Volgograd-Donbass (Mikhailkovkaya - Volgograd) HVDC Volgograd-Donbass electrode line (Mikhailkovkaya - Smile) crossing of HVDC and its electrode line
25°51′21″S 28°22′37″E / 25.85583°S 28.37694°E / -25.85583; 28.37694 (HVDC Cahora Bassa crosses its electrode line) HVDC Cahora Bassa (Apollo - Songo) HVDC Cahora Bassa electrode line (Apollo - Glastonbury Ridge) crossing of HVDC and its electrode line
50°05′30″N 97°26′12″W / 50.09167°N 97.43667°W / 50.09167; -97.43667 (Nelson River Bipole 1 & 2 cross electrode line of Nelson River Bipole 2) Nelson River Bipole 1 & 2 electrode line of Nelson River Bipole 2 crossing of HVDC and its electrode line
50°10′04″N 97°24′50″W / 50.16778°N 97.41389°W / 50.16778; -97.41389 (electrode line of Nelson River Bipole 1 crosses electrode line of Nelson River Bipole 2) electrode line of Nelson River Bipole 1 electrode line of Nelson River Bipole 2 electrode line crosses electrode line of other HVDC
60°28′46″N 17°14′12″E / 60.47944°N 17.23667°E / 60.47944; 17.23667 (Fenno-Skan 2 crosses traction current power line Tierp-Gävle) Fenno-Skan 2 (Finnbole - Rauma) Tierp-Gävle only crossing of HVDC overhead line with single phase AC line in the world
50°28′55″N 9°40′52″E / 50.48194°N 9.68111°E / 50.48194; 9.68111 (Crossing point of traction current powerlines Flieden-Bebra and Fulda-Mottgers) Flieden-Bebra Fulda-Mottgers crossing of 2 single phase AC power lines
51°01′59″N 9°34′31″E / 51.03306°N 9.57528°E / 51.03306; 9.57528 (Crossing point of traction current powerlines Bebra-Borken and Kirchheim-Körle) Bebra-Borken Kirchheim-Körle crossing of 2 single phase AC power lines
48°56′40″N 8°48′18″E / 48.94444°N 8.805°E / 48.94444; 8.805 (Crossing point of traction current powerlines Karlsruhe-Mühlacker and Vaihingen-Graben/Neudorf) Karlsruhe-Mühlacker Vaihingen-Graben/Neudorf crossing of 2 single phase AC power lines

Overhead line crossings of aerial tramways

Overhead lines should cross the route of an aerial tramway only above it, if at all.

The necessary protection distances from overhead lines to the ropes of an aerial tramway are subject to regulations concerning the construction of aerial tramways and overhead lines. In the case of an undercrossing of an aerial tramway, the maximum safety distances between the overhead line and the floor of the aerial tramway cab must be followed absolutely.

In principle, over- and undercrossings of aerial tramways are completely regulated. However, frequently at the range of the crossing section, special precautionary measures are taken. Thus, at overhead line crossings at which the overhead line runs above the rope of the aerial tramway, two catch ropes are occasionally installed to prevent the conductor from falling off the rope of the tramway in case a pylon or insulator were to break. Alternatively, auxiliary cross-bars can be installed on the pylons of the overhead line under the conductors, which prevent the conductor cables from falling in case of an insulator failure on the aerial tramway. Occasionally, the span field of the line over the aerial ropeway can be scaffolded with a rigid construction along its whole length, or at least for the span which crosses the aerial tramway.

At crossings at which the aerial tramway runs above the power line, the line is frequently installed on special masts in the crossing range, which scaffold the line in the area of the aerial tramway crossing. Such a measure is not necessary according to power line regulations, but it is often done because, in case of aerial tramway failure, it is possible to rescue people from the tram without switching off the overhead line. Such constructions may be seen at 110 kV power line crossings of the Penkenbahn at Mayrhofen, the Patscherkofelbahn at Innsbruck and south of Zermatt.

Overhead line crossings of broad rivers and straits

The two masts of the high level crossing of the River Severn estuary between England and Wales, with the Severn Bridge behind. These masts are 1.6km (1 mile) apart: a further 1.2-km line crosses the River Wye estuary to the left.

Overhead line crossings of broad rivers and of straits, if the terrain on both sides is relatively even, frequently consist of four pylons: two particularly substantial anchor pylons for bracing the conductors of the crossing section, and two tall carrying masts to keep the line high over the water. These pylons have broader cross-bars and greater distances between the cross-bars than the other pylons of the line, in order to prevent the conductor cables from striking against each other during strong winds. In contrast to normal pylons, the two carrying masts at both ends of the crossing are frequently equipped with flight safety lamps, and have stairways for easy access to the top.

Overhead line crossings of rivers and straits with spans of over 2 km are frequently prohibitively expensive to build and operate; because of the danger of wind-induced oscillatory movements of the conductor cables, it is necessary either to install very large leader distances or to mount insulators between the conductors in the area of the span. Bundle conductors, which are used for almost all extra-high voltage lines, are more susceptible to oscillations from wind forces than single conductors. Therefore single conductors must be used for the crossing section, which means the crossing section of the power line determines the maximum transmittable power.

Further, one cannot build pylons arbitrarily high at either end of the crossing section, and there is a usually a considerable minimum height because of ships crossing under the line, so there is often a high mechanical tension in the conductors at long spans. This tension requires conductors made largely of steel, which have a worse electrical conductivity than the common overhead line conductors consisting of copper, Aldrey or aluminum-encased steel, and also limits the amount of transmittable electrical power. For this reason, for crossings with a span width of more than approximately 2 km, those in charge of construction should consider laying an underwater cable as the more practicable solution.

Alternatively, it might be possible to erect one or more pylons in the water to be crossed. Such crossings can be seen occasionally in North America. They are, however, only used when it is more economical and practical to do so than to lay a cable underwater, such as when the water is not very deep and no large passage heights are needed for vessels. Also, such construction can be very problematic as far as getting legal permission to build, because pylons standing in the water are likely to be considered dangerous obstacles for ships, especially in foggy conditions.

In some cases on bridges small crossing a wider waterway pylons or crossbars for the conductors can be mounted. Such a solution, which may lead to safety problems at bridge maintenance, was for example realized at the Danish Storstrøm Bridge.

It is quite likely that overhead line crossings of broad waters can be replaced with underwater cables. The overhead line crossing the Strait of Messina — which, with a span of 3646 meters, was one of the longest overhead line crossings in the world, with 200-meter pylons among the highest in the world — was replaced by a submarine cable, because of its small maximum transmittable electrical power.

Overhead line crossing of valleys

Overhead line crossings of valleys consist of two anchor pylons, one at either end of the valley. If the topography of the valley is suitable, these do not need to be very high. In very wide valleys, it is better to use a pylon for each phase in order to achieve sufficient distance between the conductors. In these cases there is frequently a further anchor pylon behind the crossing, used in order to realize the angle change of the conductor cables behind these. The problems associated with large spans also exist in these cases, but these can be easily and economically ameliorated, if the topography does not require high crossing pylons, by using a separate pylon for each conductor.

Structures

A crossing pylon is used for crossing over a body of water or a valley. Due to the long [span width|span]], crossing pylons across rivers and sea straits are frequently taller than standard pylons. They may have marking lamps, and unlike standard pylons, often have stairways for easy access to the top. In many cases, their height makes them ideal for carrying radio antennas and transmitting equipment.

Crossing pylons for valleys, depending on the local topography, are not necessarily tall, but the distance between the conducting cables must be sufficient to prevent high winds knocking the conductors into one another; these pylons have wide crossbars to prevent this. For very long spans each phase has a separate pylon, particularly if the pylons are short.

Special crossing pylons are often used where aerial tramways cross power lines. These pylons are designed with integral scaffolding so that the tramway cars can be reached without touching a live power line. This enables passengers to be rescued from the tramway if it fails without cutting the power from the power line. Such installations can be found, for example, south of Zermatt, Switzerland; at the Patscherkofelbahn near Innsbruck, Austria; and at the Penkenbahn in Mayrhofen, Austria.

References

This article draws heavily on the corresponding article in the German-language Wikipedia.

See also


Wikimedia Foundation. 2010.

Игры ⚽ Поможем сделать НИР

Look at other dictionaries:

  • Suez Canal overhead line crossing — Overhead line crossing The Suez Canal overhead line crossing is an important electrical power line built across the Suez Canal in 1998, located in the city of Suez, Suez Governorate, Egypt. It is designed for two 500 kV circuits. Because the… …   Wikipedia

  • Bosporus overhead line crossing III — is the third overhead line crossing of the Bosporus. Bosporus overhead line crossing III is designed for four 420kV circuits, but can be used after some reengineering work also for 800kV lines. The pylons on which the 1884m crossing span is… …   Wikipedia

  • Bosporus overhead line crossing I — The Bosporus overhead line crossing I is the first powerline crossing the Bosporus. It was inaugurated in 1957 and it is designed for 154kV circuits.ee also* List of towersExternal links* http://maps.google.com/maps?q= t=k ie=UTF8 z=18… …   Wikipedia

  • Bosporus overhead line crossing II — is the second powerline across Bosporus. It is designed for two 420kV circuits and it went in service in 1983. See also * List of towers External links * http://maps.google.com/maps?q= t=k ie=UTF8 om=0 z=18 ll=41.177168,29.069846… …   Wikipedia

  • Crossing pylon — A crossing pylon is an electricity pylon for a crossing of an overhead line crossing over a body of water, or a valley.In order to allow ships passing underneath, crossing pylons across wide rivers and sea straits are frequently taller than… …   Wikipedia

  • Overhead lines — This article is about the transmission of electrical power to road and rail vehicles. For transmission of bulk electrical power to general consumers, see Electric power transmission. For powerlines mounted on pylons, see overhead power line.… …   Wikipedia

  • Overhead power line — This article is about power lines for general transmission of electrical power. For overhead lines used to power road and rail vehicles, see Overhead lines. Transmission lines in Lund, Sweden …   Wikipedia

  • overhead railway — noun a railway that is powered by electricity and that runs on a track that is raised above the street level • Syn: ↑elevated railway, ↑elevated railroad, ↑elevated, ↑el • Hypernyms: ↑railway, ↑railroad, ↑railroad line, ↑ …   Useful english dictionary

  • The Cassandra Crossing — Infobox Film name = The Cassandra Crossing imdb id = 0074292 producer = Lew Grade director = George Pan Cosmatos writer = George Pan Cosmatos, Robert Katz starring = Ava Gardner Richard Harris Burt Lancaster Sophia Loren Martin Sheen O.J. Simpson …   Wikipedia

  • Morristown Line —   Morristown Line …   Wikipedia

Share the article and excerpts

Direct link
Do a right-click on the link above
and select “Copy Link”