Controller (control theory)

Controller (control theory)

In control theory, a controller is a device which monitors and affects the operational conditions of a given dynamical system. The operational conditions are typically referred to as output variables of the system which can be affected by adjusting certain input variables. For example, the heating system of a house can be equipped with a thermostat (controller) for sensing air temperature (output variable) which can turn on or off a furnace or heater when the air temperature becomes too low or too high.

In this example, the thermostat is the controller and directs the activities of the heater. The heater is the processor that warms the air inside the house to the desired temperature (setpoint). The air temperature reading inside the house is the feedback. And finally, the house is the environment in which the heating system operates.

The notion of controllers can be extended to more complex systems. In the natural world, individual organisms also appear to be equipped with controllers that assure the homeostasis necessary for survival of each individual. Both human-made and natural systems exhibit collective behaviors amongst individuals in which the controllers seek some form of equilibrium.

Contents

Types of Controlling System

In control theory there are two basic types of control. These are feedback and feed-forward. The input to a feedback controller is the same as what it is trying to control - the controlled variable is "fed back" into the controller. The thermostat of a house is an example of a feedback controller. This controller relies on measuring the controlled variable, in this case the temperature of the house, and then adjusting the output, whether or not the heater is on. However, feedback control usually results in intermediate periods where the controlled variable is not at the desired set-point. With the thermostat example, if the door of the house were opened on a cold day, the house would cool down. After it fell below the desired temperature (set-point), the heater would kick on, but there would be a period when the house was colder than desired.

Feed-forward control can avoid the slowness of feedback control. With feed-forward control, the disturbances are measured and accounted for before they have time to affect the system. In the house example, a feed-forward system may measure the fact that the door is opened and automatically turn on the heater before the house can get too cold. The difficulty with feed-forward control is that the effect of the disturbances on the system must be accurately predicted, and there must not be any unmeasured disturbances. For instance, if a window were opened that was not being measured, the feed-forward-controlled thermostat might still let the house cool down.

To achieve the benefits of feedback control (controlling unknown disturbances and not having to know exactly how a system will respond to disturbances) and the benefits of feed-forward control (responding to disturbances before they can affect the system), there are combination's of feedback and feed-forward that can be used.

Some examples of where feedback and feed-forward control can be used together are dead-time compensation, and inverse response compensation. Dead-time compensation is used to control devices that take a long time to show any change to a change in input, for example, change in composition of flow through a long pipe. A dead-time compensation control uses an element (also called a Smith predictor) to predict how changes made now by the controller will affect the controlled variable in the future. The controlled variable is also measured and used in feedback control. Inverse response compensation involves controlling systems where a change at first affects the measured variable one way but later affects it in the opposite way. An example would be eating candy. At first it will give you lots of energy, but later you will be very tired. As can be imagined, it is difficult to control this system with feedback alone, therefore a predictive feed-forward element is necessary to predict the reverse effect that a change will have in the future. '''

Types of controllers

Most control valve systems in the past were implemented using mechanical systems or solid state electronics. Pneumatics were often utilized to transmit information and control using pressure. However, most modern control systems in industrial settings now rely on computers for the controller. Obviously it is much easier to implement complex control algorithms on a computer than using a mechanical system.

For feedback controllers there are a few simple types. The most simple is like the thermostat that just turns the heat on if the temperature falls below a certain value and off it exceeds a certain value (on-off control).

Another simple type of controller is a proportional controller. With this type of controller, the controller output (control action) is proportional to the error in the measured variable.


In feedback control, it is standard to define the error as the difference between the desired value (setpoint) ysand the current value (measured) y. If the error is large, then the control action is large. Mathematically:

u(t) = Kc * e(t) + u0

where

u(t) represents the control action (controller output),
e(t) = ys(t) − y(t) represents the error,
Kc represents the controller's gain, and
uo represents the steady state control action (bias) necessary to maintain the variable at the steady state when there is no error.

It is important that the control action u counteracts the change in the controlled variable y (negative feedback). There are then two cases depending on the sign of the process gain.

In the first case the process gain is positive, so an increase in the controlled variable (measurement) y requires a decrease in the control action u (reverse-acting control). In this case the controller gain Kc is positive, because the standard definition of the error already contains a negative sign for y.

In the second case the process gain is negative, so an increase in the controlled variable (measurement) y requires an increase in the control action u (direct-acting control). In this case the controller gain Kc is negative.

A typical example of a reverse-acting system is control of temperature (y) by use of steam (u). In this case the process gain is positive, so if the temperature increases, the steam flow must be decreased to maintain the desired temperature. Conversely, a typical example of a direct-acting system is control of temperature using cooling water. In this case the process gain is negative, so if the temperature increases, the cooling water flow must be increased to maintain the desired temperature.

Although proportional control is simple to understand, it has drawbacks. The largest problem is that for most systems it will never entirely remove error. This is because when error is 0 the controller only provides the steady state control action so the system will settle back to the original steady state (which is probably not the new set point that we want the system to be at). To get the system to operate near the new steady state, the controller gain, Kc, must be very large so the controller will produce the required output when only a very small error is present. Having large gains can lead to system instability or can require physical impossibilities like infinitely large valves.

Alternates to proportional control are proportional-integral (PI) control and proportional-integral-derivative (PID) control. PID control is commonly used to implement closed-loop control.

Open-loop control can be used in systems sufficiently well-characterized as to predict what outputs will necessarily achieve the desired states. For example, the rotational velocity of an electric motor may be well enough characterized for the supplied voltage to make feedback unnecessary.

The drawback of open-loop control is that it requires perfect knowledge of the system (i.e. one knows exactly what inputs to give in order to get the desired output), and it assumes there are no disturbances to the system.

See also

References


Wikimedia Foundation. 2010.

Игры ⚽ Нужен реферат?

Look at other dictionaries:

  • Control theory — For control theory in psychology and sociology, see control theory (sociology) and Perceptual Control Theory. The concept of the feedback loop to control the dynamic behavior of the system: this is negative feedback, because the sensed value is… …   Wikipedia

  • control theory — Field of applied mathematics relevant to the control of certain physical processes and systems. It became a field in its own right in the late 1950s and early 60s. After World War II, problems arising in engineering and economics were recognized… …   Universalium

  • Perceptual control theory — (PCT) is a psychological theory of animal and Human behavior originated by maverick scientist William T. Powers. In contrast with other theories of psychology and behavior, which assume that behavior is a function of perception that perceptual… …   Wikipedia

  • Dual control theory — is a branch of control theory that deals with the control of systems whose characteristics are initially unknown. It is called dual because in controlling such a system the controller s objectives are twofold: (1) Action: To control the system as …   Wikipedia

  • Controller — may refer to: Contents 1 Occupations 2 Computing and electronics 3 Other devices …   Wikipedia

  • H-infinity methods in control theory — H ∞ (i.e. H infinity ) methods are used in control theory to synthesize controllers achieving robust performance or stabilization. To use H ∞ methods, a control designer expresses the control problem as a mathematical optimization problem and… …   Wikipedia

  • Control system (disambiguation) — A control system is a device or set of devices to manage, command, direct or regulate the behavior of other devices or systems. A control mechanism is a process used by a control system. Control system may refer to: Contents 1 General control… …   Wikipedia

  • Control engineering — Control systems play a critical role in space flight Control engineering or Control systems engineering is the engineering discipline that applies control theory to design systems with predictable behaviors. The practice uses sensors to measure… …   Wikipedia

  • Control reconfiguration — is an active approach in control theory to achieve fault tolerant control for dynamic systems [1]. It is used when severe faults, such as actuator or sensor outages, cause a break up of the control loop, which must be restructured to prevent… …   Wikipedia

  • Control system — For other uses, see Control system (disambiguation). A control system is a device, or set of devices to manage, command, direct or regulate the behavior of other devices or system. There are two common classes of control systems, with many… …   Wikipedia

Share the article and excerpts

Direct link
Do a right-click on the link above
and select “Copy Link”